Renovation guide · Bathrooms

Bathroom exhaust fans: size, ducting and controls

A fan’s rating is measured in a lab. What it moves in your bathroom depends on the duct behind it, and that’s the part nobody sees.

6 min readUpdated By SS Carpentry and Renovations

Section through a bathroom and the attic above it: an exhaust fan in the ceiling over the tub, an insulated duct rising through the attic to a capped outlet on the roof, kept clear of the vented soffit, with a gap under the bathroom door and a switch on the wall.

Key takeaways

  • Ontario’s Building Code asks for a bathroom fan rated at least 25 L/s (about 53 cfm), on a switch in the room.
  • Size it by floor area: about 1 cfm per square foot, never under 50, with more for a large bathroom.
  • The duct decides what the fan really moves: at the pressure fans are rated at, a 4″ duct is allowed only 2 m, a 6″ duct 16 m.
  • It must end outside, never in the attic, and run about 20 minutes after each shower.

Why does a bathroom need an exhaust fan?

A shower fills a small room with water vapour, and moisture is what mould needs. Health Canada’s advice is to keep indoor humidity between 30% and 50%. In the room that makes the most moisture, the exhaust fan is what keeps it there.

It protects the waterproofing too. Whatever is behind the tile, the membrane maker in our guide to what goes behind shower tile still calls for ventilation to manage water vapour and condensation.

What does Ontario’s Building Code ask for?

Ontario 2024 Building Code requirements for bathroom exhaust in a house (Division B, Subsection 9.32.3)
ArticleWhat it requires
9.32.3.7An exhaust fan rated at least 25 L/s in every bathroom (unless the house’s main ventilation system draws air from it), on a manual switch in the room. A humidity control can be added, but the switch must still turn the fan on.
9.32.3.10Fan capacity is rated at 25 Pa of pressure. A fan within 1 m of duct of the room is limited to 3.5 sones on HVI’s scale (2.5 on CSA’s).
9.32.3.11The duct never discharges into the attic or any enclosed space, is insulated to RSI 0.5 through unheated space, has sealed joints and doesn’t sag or get crushed.
9.32.3.13The outlet has a backdraft damper and sits at least 1.8 m from air intakes and vented soffits, and at least 100 mm above the ground.
Section through a bathroom and the attic above it: an exhaust fan in the ceiling over the tub, an insulated duct rising through the attic to a capped outlet on the roof, kept clear of the vented soffit, with a gap under the bathroom door and a switch on the wall.ABCDEF
  • A: Fan in the ceiling, over the shower or tub, rated at least 25 L/s (about 53 cfm)
  • B: Duct insulated to at least RSI 0.5 through the cold attic, joints sealed
  • C: Out through the roof or a wall, with a backdraft damper: never into the attic
  • D: Outlet at least 1.8 m from vented soffits and air intakes
  • E: A gap under the door (about ¾″) lets replacement air in
  • F: A manual switch in the room, which turns the fan on whatever a timer or humidity control is set to
A bathroom fan from the room to the roof. Each mark is one rule from the table above, plus the gap under the door that lets air back in.

How big a fan does a bathroom need?

The Code’s floor is 25 L/s, about 53 cfm. The fan makers’ trade body, the Home Ventilating Institute (HVI), sizes by floor area: 1 cfm per square foot, and never under 50 cfm, for a bathroom up to 100 sq ft. A larger room adds 50 cfm for each toilet, shower and tub, and 100 for a jetted tub.

  • A 5′ × 8′ bathroom is 40 sq ft: HVI’s 50 cfm minimum, and the Code’s 25 L/s (53 cfm) as the floor.
  • An 8′ × 10′ ensuite is 80 sq ft: about 80 cfm.
  • A 12′ × 10′ ensuite with a toilet, a shower and a tub is over 100 sq ft: 150 cfm.

Put the fan over the shower or tub where you can, using a fan approved for that wet location, and give an enclosed toilet room its own. For noise, check the sone rating on the HVI label: one sone is about a quiet fridge in a quiet kitchen, and lower is quieter. The Code caps a bathroom fan at 3.5 sones on HVI’s scale.

Why does the duct matter as much as the fan?

A fan’s airflow rating is measured against a set resistance: 25 pascals, or 0.1″ of water, for a bathroom fan. Every metre of duct adds to it. Ask more of the fan than it was rated against and it moves less air than the number on the box.

The Code’s duct table shows how quickly this bites. For a fan moving 25 L/s at that rated pressure, the longest duct it allows:

The longest duct allowed for a 25 litre-per-second bathroom fan rated at 25 pascals: none at 75 mm, 2 metres at 100 mm, 6 metres at 125 mm and 16 metres at 150 mm.75 mm3″not allowed100 mm4″2 m125 mm5″6 m150 mm6″16 m
Longest duct for a 25 L/s fan rated at 25 Pa, from the Building Code’s Table 9.32.3.11.-A. A fan rated at a higher pressure is allowed more: at 50 Pa, 6 m on a 100 mm duct. Flexible duct counts as the next size down, or as twice its length.

So a 4″ duct run 5 m across an attic to a gable is too long for that fan. Either the duct gets bigger or shorter, or the fan is chosen for a higher pressure. Through the cold attic the duct is insulated, so the moist air doesn’t condense inside it, and it ends outside, through the roof or a wall with a damper. Never into the attic.

How long should a bathroom fan run?

HVI recommends at least 20 minutes after each use, with a timer or another control that keeps it running after you leave. A humidity sensor that starts the fan automatically is a good addition; the Code just asks that the manual switch can still turn it on whatever the sensor is set to.

The fan also needs air to replace what it pulls out. HVI asks for at least ¾″ under the bathroom door. A thicker new floor can quietly close that gap, so it’s worth checking when the flooring changes.

When is the best time to fix a bathroom fan?

When the ceiling is open. In a bathroom renovation the old fan comes out with everything else, and a larger duct, a better route to the outside or a new outlet is far easier than through a finished ceiling. Moving a fan or adding a circuit is electrical work: almost all of it needs a notification to the Electrical Safety Authority, which our guide to permits for renovation work in Ottawa explains.

On the bathrooms we renovate, electrical work goes to licensed electricians, and a bathroom typically takes 3 to 4 weeks on site. If the bathroom is one part of the home renovations we carry out in Ottawa, the fan and its duct belong on the list at the estimate.

Guidance only, not a design or code ruling. The Ontario Building Code and each fan’s installation instructions set what a bathroom fan must meet.

Questions

Quick answers

Ontario’s Building Code asks for at least 25 L/s, about 53 cfm. The Home Ventilating Institute sizes it at 1 cfm per square foot of floor, never under 50 cfm, for bathrooms up to 100 sq ft; larger bathrooms add 50 cfm for each toilet, shower and tub, and 100 for a jetted tub.

No. Ontario’s Building Code says exhaust ducts must not discharge into heated or unheated enclosed spaces. The duct goes to the outside, through a roof or wall outlet with a backdraft damper, insulated to RSI 0.5 where it passes through the cold attic.

At least 20 minutes after each use, the Home Ventilating Institute recommends, with a timer or other control that keeps it running after you leave.

It depends on the length and the fan’s rated pressure. In the Building Code’s table, a 25 L/s fan rated at 25 Pa is allowed 2 m of 100 mm (4″) duct, 6 m of 125 mm (5″) and 16 m of 150 mm (6″). Flexible duct counts as the next size down.

Sources

Every figure, with its source

No figure on this page is published from memory. Each one links to the official page it was read from, on the date shown. Guide last reviewed October 27, 2026.

Sourced claims used in this guide
RefClaimPrimary sourceRead
OBC-9.32.3.7
Div. B 9.32.3.7.(4), (6) and (8)
Where an exhaust air intake for the principal ventilation fan is not located in a bathroom or water-closet room, a supplemental exhaust fan with a rated capacity not less than 25 L/s shall be installed in that bathroom or water-closet room. It shall be controlled by a manual switch located in the room served; where a dehumidistat or other automatic control is added, the manual switch shall be capable of activating the fan regardless of the setting of the automatic control.Ontario 2024 Building Code Compendium (O. Reg. 163/24) (opens in a new tab)
OBC-9.32.3.10
Div. B 9.32.3.10.(1)–(3), (6); Tables 9.32.3.10.-A and -B
Capacity ratings for fans are determined to CAN/CSA-C260-M or HVI Publication 916, measured at 25 Pa (0.1 inch water column) external static pressure for fans other than those with ducts on both sides or exhaust-only principal fans. Supplemental exhaust fans installed in bathrooms with less than 1 m of duct to the room shall have a sound rating of not more than 2.5 sones (CAN/CSA-C260-M) or 3.5 sones (HVI 915) at the required flow rate.Ontario 2024 Building Code Compendium (O. Reg. 163/24) (opens in a new tab)
OBC-9.32.3.11
Div. B 9.32.3.11.(1)–(3), (7), (8), (11)
Exhaust ducts serving only a bathroom or water-closet room are permitted to be of combustible material, provided they are reasonably airtight and impervious to water. Exhaust ducts shall not discharge into heated or unheated enclosed spaces. Where an exhaust duct passes through an unheated space, it shall be insulated to not less than RSI 0.5. Ductwork shall be installed to avoid crushing and supported to prevent sagging, and joints sealed with mastic, metal foil duct tape or the manufacturer’s specified sealants. Flexible duct may be sized by choosing the next higher diameter in Table 9.32.3.11.-A or the diameter for a duct twice as long as the actual length.Ontario 2024 Building Code Compendium (O. Reg. 163/24) (opens in a new tab)
OBC-TABLE-9.32.3.11.-A
Div. B Table 9.32.3.11.-A
Equivalent duct sizes: for a maximum airflow of 25 L/s and a fan external static pressure of 25 Pa, the maximum length of duct is 0 m at 75 mm diameter, 2 m at 100 mm, 6 m at 125 mm and 16 m at 150 mm. At 50 Pa the same airflow allows 6 m at 100 mm and 18 m at 125 mm.Ontario 2024 Building Code Compendium (O. Reg. 163/24) (opens in a new tab)
OBC-9.32.3.13
Div. B 9.32.3.13.(4), (5), (8), (11)
Exhaust outlets that discharge air containing moisture, such as bathroom ventilation outlets, shall be located at least 1 800 mm from air intakes and vented soffits (or the soffit unvented or blocked as set out). The bottom of an exhaust outlet shall be at least 100 mm above finished ground, and exhaust outlets other than those serving heat recovery ventilators shall incorporate backdraft dampers.Ontario 2024 Building Code Compendium (O. Reg. 163/24) (opens in a new tab)
OBC-9.32.3.8
Div. B 9.32.3.8.(1), (2), (6)–(8)
In dwelling units that contain a fuel-fired space-heating or water-heating appliance of other than direct-vented or mechanically vented types, any mechanical air exhausting device other than the principal ventilation fan (at its normal rate) shall be provided with outdoor makeup air supplied by a fan, except as provided in Sentences (6) to (8), which include houses where a depressurization test shows the appliances are not put at risk.Ontario 2024 Building Code Compendium (O. Reg. 163/24) (opens in a new tab)
HVI-SIZINGHVI recommends intermittent bathroom ventilation of 1 CFM per square foot of floor area, with a minimum of 50 CFM, for bathrooms under 100 sq ft; above 100 sq ft, add 50 CFM each for a toilet, shower and bathtub and 100 CFM for a jetted tub. An enclosed toilet should have its own fan. Fans approved for wet areas should be located over the shower or tub whenever possible. Bathroom doors need at least 3/4″ clearance to the finished floor for makeup air. A timer or other control that keeps ventilation running for a minimum of 20 minutes after each use should be installed. Continuous ventilation at a minimum of 20 CFM may be used instead of an intermittent 50 CFM fan.Home Ventilating Institute: How Much Ventilation Do I Need? (opens in a new tab)
HVI-RATINGSHVI-Certified fans carry tested ratings for airflow in cubic feet per minute (CFM) and sound in sones, listed in the HVI-Certified Products Directory. One sone is approximately the sound of a quiet refrigerator in a quiet kitchen; the lower the sone rating, the quieter the fan.Home Ventilating Institute: HVI-Certified Ventilation Performance (opens in a new tab)
HC-RHMaintain relative humidity between 30% and 50%; run a dehumidifier in the basement to help reduce dampness year-round, if necessary; consider removing any carpets from the basement floor; fix the underlying moisture problem first to prevent mould from returning.Health Canada: Guide to addressing moisture and mould indoors (opens in a new tab)
ESA-NOTIFICATIONAlmost all electrical work in Ontario must be reported to the Electrical Safety Authority by a notification of work, which should be filed before the work starts. “Having a building permit isn't the same as filing an electrical notification. You may need both.”Electrical Safety Authority: What you need to know (opens in a new tab)